| Skyline College | Bid No. 86513 |
Building 8 Swing Space Revisions |
Section 16140 WIRING DEVICES
Part 1 GENERAL
1.01. Description of Work
A. The work of this section consists of:
1. Furnishing, installing, and connecting all duplex receptacles complete with wall plates and/or covers, as shown on the Drawings.
2. Furnishing, installing and connecting all single pole and three-way switches complete with wall plates and or handle operators, as shown on the Drawings.
1.02. Related Work:
A. See the following specification sections for work related to the work of this section:
1. 16110 Conduits, Raceways and Fittings.
2. 16120 Low Voltage Wire and Cable.
3. 16130 Junction and Pull Boxes.
1.03. Standards and Codes:
A. Work and material shall be in compliance with and according to the requirements of the latest revision of the following standards and codes.
1. California Electrical Code (CEC).
2. Federal Specifications (FS):
a. W-C-596 Series General Specifications for Electrical Plugs and Receptacles.
b. W-S-896F General Specifications for Flush Mounted Toggle and Lock Switches.
3. National Electrical Manufacturers Association (NEMA) Publication:
a. WD1 General Purpose Wiring Devices.
4. Underwriters Laboratories (UL) Standards:
a. 20 General-Use Snap Switches.
b. 498 Attachment Plugs and Receptacles.
c. 514A Electrical Metallic Outlet Boxes.
d. 514B Fittings for Cable and Conduit.
e. 943 Ground-Fault Circuit-Interrupters.
1.04. Submittals:
A. As specified in Division 1 and Section 16010.
B. Catalog Data: Provide manufacturers descriptive literature properly marked to identify the items to be supplied.
C. Single Submittal: A single complete submittal is required for all products covered by this Section.
Part 2 PRODUCTS
2.01. Receptacles:
A. General - Receptacles shall be heavy duty, high abuse, grounding type conforming to NEMA WD1 and UL 498 Standards.
B. Duplex Receptacles:
1. Receptacles shall be specification grade, rated 20 ampere, two-pole, 3-wire, 120 volt, NEMA 5-20 configuration, self-grounding with screw terminals. Color shall be ivory unless otherwise noted.
2. Devices shall have a nylon composition face with a nylon or melamine body. Units shall comply with Federal Specification W-C-596 and meet UL 498 test requirements.
3. Manufacturer: Hubbell #HBL5362 Series, Leviton #5362 Series.
C. GFCI Receptacles:
1. Device shall be rated 20 ampere, 2-pole, 3-wire, 120 volt, conforming to NEMA 5-20R configuration. Face shall be nylon composition. Unit shall have an LED type red indicator light, test and reset push buttons. Color shall be ivory unless otherwise noted.
2. GFCI component shall meet UL 943 Class A standards with a tripping time of 1/40 second at 5 milliamperes current unbalance. Operating range shall extend from -31F to 158F. Unit shall have transient voltage protection and shall be ceramic encapsulated for protection against moisture.
3. Manufacturer: Hubbell #GF5362 Series, Leviton #6898 Series.
D. GFCI Blank Face Devices:
1. Device shall be rated 20 ampere, 2-pole, 3-wire, 120 volt, blank face, dead front. Face shall be nylon composition. Unit shall have a test and reset push buttons. Color shall be ivory unless otherwise noted.
2. GFCI component shall meet UL 943 Class A standards with a tripping time of 1/40 second at 5 milliamperes current unbalance. Operating range shall extend from -31F to 158F. Unit shall have transient voltage protection and shall be ceramic encapsulated for protection against moisture.
3. Manufacturer: Hubbell #GF5350IA Series, Leviton #6490 Series.
2.02. Switches:
A. Switches shall be rated 20 amperes to 120 or 277 volts ac only. Units shall be flush mounted, self-grounding, quiet operating toggle devices. Color shall be ivory unless otherwise noted.
B. Units shall conform to Federal Specifications W-S-896, UL 20 and NEMA WD1.
C. Timed switches: Shall be as designed by Paragon Electric Company # ET2000f or Watt Stopper TS-100 rated for the voltage specified on drawings. Time out shall be adjustable from 5 minutes up to 12 hours. Unit shall be provided with warning alarm.
2.03. Plates:
A. General - Plates shall be of the style and color to match the wiring devices, and of the required number of gangs. Plates shall conform to NEMA WD1, UL 514, and FS W-P-455A. Plates on finished walls shall be non-metallic. Plates on unfinished walls and on fittings shall be of zinc plated steel or case metal and shall have rounded corners and beveled edges.
B. Non-Metallic: Plates shall be plain with beveled edges and shall be nylon or reinforced fiberglass.
C. Cast Metal: Plates shall be cast or malleable iron covers with gaskets so as to be moisture resistant or weatherproof.
D. Blank Plates: Cover plates for telephone and data outlets shall match adjacent device wall plates in appearance.
Part 3 EXECUTION
3.01. Installation of Wiring Devices:
A. Interior Locations: In finished walls, install each device in a flush mounted box with washers as required to bring the device mounting strap level with the surface of the finished wall. On unfinished walls, surface mount boxes level and plumb.
B. Mounting Heights: Measure locations of wall outlets from the finished floor to the center of the outlet box. Adjust boxes so that the front edge of the box shall not be farther back from the finished wall plane than 1/4-inch. Adjust boxes so that they do not project beyond the finished wall. Unless otherwise noted, height above finished floor shall be as follows:
1. Receptacles 18 Inches from floor
2. Toggle Switches 48 Inches from floor
C. Receptacles:
1. Ground each receptacle using a grounding conductor, not a yoke or screw contact.
2. Install receptacles with connections spliced to the branch circuit wiring in such a way that removal of the receptacle will not disrupt neutral continuity and branch circuit power will not be lost to other receptacles in the same circuit.
3.02. Installation of Wall Plates:
A. General - Plates shall match the style of the device and shall be plumb within 1/16-inch of the vertical or horizontal.
B. Interior Locations, Finished Walls: Install non-metallic plates so that all four edges are in continuous contact with the finished wall surfaces. Plaster filling will not be permitted. Do not use oversized plates or sectional plates.
C. Interior Locations, Unfinished Walls: Install stainless steel or cast metal cover plates.
D. Exterior Locations: Install cast metal plates with gaskets on wiring devices in such a manner as to provide a rain tight weatherproof installation. Cover type shall match box type.
E. Future Locations: Install blanking cover plates on all unused outlets.
3.03. Tests:
A. Receptacles:
1. Test receptacles for blade and ground plug tension prior to installation. Do not install any receptacle having less than 16 oz. individual blade retention.
2. After installation of receptacles, energize circuits and test each receptacle to detect lack of ground continuity, reversed polarity, and open neutral condition.
end of section